Modification of Cimdor 1.2 Kilowatt Power Supply
Initial Problem:
Electrical connections between the high voltage
transformer and underside of insulating board are of the
female push on type. Over time these connections loose
their integrity and become electrically intermittent.
This situation causes excessive heating and has an
avalanche effect on the power supply. Inevitably, the
supply fails and a time consuming repair or complete
replacement is required.
Purpose of Modification:
To alleviate the problems associated with
intermittent connections and the overheating of the
insulating board.
MES Solution:
· Replace
insulating board.
· Replace
all wiring on capacitors, high voltage rectifier, and
upper section of insulating board.
· Replace
push on type electrical connections from high voltage
transformer to underside of insulating board with ring
type terminals. Insure these are held securely with lock
washers and double nuts.
· Replace
the high voltage rectifier assembly with a more
modernized version of higher ratings.
· Thoroughly
clean the outer enclosure of the power supply.
· Test
the power supply under load
End Result:
· More
reliable operation from power supply.
· Reduced
down time.
· Greater
efficiency.